Features

※ High efficiency,COP reach to over 30
※ Comfortable:cool but no moisture added
※ System can work well in 50 environment,and with ambient temperature rises, the cooling ability will increase
※ The supplying air temperature reach to web bulb temperature
※ Easy maintenance
※ Intelligent control:Take central controller to auto adjust the airflow,can be used separately in dry
※ Group control
※ Environment friendly

Working Principle

Working flow is divided into many small flows which pass the dry channels in the lower part of the cooling core.

Every small flow is cooled by al the small flows before it crossing pass in another side channels called wet channels.

Dry and wet channels are placed one by one with thinner wall separately made of special materials.

Heat transfers but no water exchanges. Working flows are cooled down but no moisture added.

Then every flow goes into wet channels placed its two sides by through its controlling holes, contact with the counter-flow water.

It is cooled and moisture added. Then bring the heat passed from its two-side. Its temperature is lowed down continuously at the end;

its temperature goes under the web-bulb of its beginning flow, near the dew-point temperature. Supplying flow also is divided into many

small flows, go through the dry channels placed in the part of the core. They are cooled by their own two-side working flows crossing

flow in the wet channels. No any moisture is added, but the temperature is cooled down under the wet-bulb of its beginning flow.

 
Application Fields

Dimension Drawing
 

Model

AJL10-DJ20A

AJL75-DJ150A

AJL12-JZ20A

Air Supply Rate(m3/h)

2000

15000

2000

Fresh Air Cooling Capacity(Kw)

10

75

12

Air Outlet Residual pressure (Pa)

30

150

30

Power Resource(V/Hz)

220/50

380/50

220/50

Input Power(Kw)

0.37

5.65

0.37

COP(Kw/Kw)

27

13

32

Wet Bulb Efficiency(%)

100

100

100

Run Current(A)

1.7

11.5

1.7

Fresh Air Rate(%)

/

100

/

Water Consumption(l/h)

12

90

12

Dimension Drawing (mm)

820*895*1570

3965*1720*2625

1755*415*1760

Net Weight(Kg)

150

1100

150

Noise bB(A)

67

80

67

Supply Air(mm)

500*150

580*675

370*150

Exhaust Air(mm)

745*155

2000*250

200*135*2

Function

Sensible Cooling

Sensible Cooling

Cooling& Humidifyling

Motor Speed

Varialbe Speeds By Controlled Silicon

3-phase,2-speed

Variable Speeds By Controlled Silicon

Controller Type

2012 LCD Control

2012 LCD Control

2012 LCD Control